Classic Series
Classic Plus/Office Pro

>Classic 40 & Classic 60
Specifications
Office Pro 10 Office Pro 12 Office Pro 18 Office Pro 24 Office Pro 36 Office Pro 60 Classic Plus 14 Classic Plus 26 Classic 10 Classic 18
Call For Prices
Cooling Capacity
(95° at 60% RH) (Btu/Hr)
9,600 11,800 16,800 23,300 36,000 59,500 13,200 24,000 10,000 18,000
Electronic Features
(Control Panel/Thermostat Control)
Progr.
/Elect.
Progr.
/Elect.
Progr.
/Elect.
Progr.
/Elect.
Progr.
/Elect.
Progr.
/Elect.
Elect. Elect. Mech. Mech.
Air Flow (CFM, High/Low) Evaporator 205/175 410/380 540/500 630/545 990/825 1940/1770 440/380 708/600 270 530
Air Flow (CFM, High/Low) Condenser 370 820/715 770/710 870/760 1480/1060 2830/2650 880/760 1680/1460 740 1180
Operating Conditions
(Min-Max°F)
65-95 65-95 65-95 65-95 65-95 65-105 70-113 70-113 68-105 68-105
Voltage 115/1 115/1 115/1 208/230/1 208/230/1 208/230/1 115/1 208/230/1 115/1 208/230/1
Min-Max Voltage 105-125 105-125 105-125 195-250 198-253 195-250 105-125 190-250 105-125 190-250
Power Consumption (KW) 1.25 1.4 1.7 2.7 4.4 7.1 1.3 3.1 1.1 2.1
Current Consumption (AMPS) 11.5 11.2 15.6 11.2 19.7 33 12.3 15.6/14 10.6 10.8/10
Circuit Breaker Size (AMPS) 15 15 20 20 30 50 15 20 15 15
NEMA Plug Configuration 5-15 5-15 5-20 6-20 6-30 6-50 5-15 6-20 5-15 6-15
Power Cord (Gauge/Length) 14AWG
(3-core)
6 ft
14AWG
(3-core)
10 ft
12AWG
(3-core)
10 ft
12AWG
(3-core)
6 ft
10AWG
(3-core)
6 ft
6AWG
(3-core)
6 ft
14AWG
(3-core)
10 ft
12AWG
(3-core)
6 ft
14AWG
(3-core)
6 ft
14AWG
(3-core)
6 ft
Dimensions W X D X H (IN) 22x14x38 21x27x44 21x27x44 21x27x47 30X44X52 30x52x64 19x26x41 19x29x47 19x26x41 19x26x41
Weight
(Net Weight/ Shipping Weight)(LBS)
130/172 165/195 177/207 210/250 440/540 625/755 153/195 235/265 145/170 167/200
Humidity Removed at 60% RH (GAL/HR) 0.52 0.62 0.97 1.26 2.16 1.97 0.69 1.38 0.66 1.19
Drain Tank Capacity (GAL) 2.4 5 5 5 2 @ 5 gal Auto Pump 5 5 5 5
R-22 Charge 1.61 lb 0.95 lb 1.54 lb 2.14 lb 2.4 lb 6.83 lb 1.5 lb 1.87 lb 1.15 lb 1.59 lb
Sound Level(db, High/Low) w/Duct 58/56 52/50 61/59 63/61 65/62 69/67 57/55 66/64 55 63
Max. Duct Length
(Cold Duct Hose/Hot Duct Hose)
N/A /
25 ft
30 ft/
60 ft
25 ft/
100 ft
50 ft/
45 ft
40 ft/
60 ft
40 ft/
100 ft
30 ft/
60 ft
60 ft/
45 ft
40 ft/
60 ft
50 ft/
60 ft
Field-Installed accessories
12" Hot Duct Flange N/A Included Included Included Included Included 12F 12F 12F 12F
2 X 2 Ceiling Tile w/Hose CT-10 CT-12 CT-12 CT-12 CT-16 CT-16 CT-12 CT-12 CT-12 CT-12
Cond. Return Air Plenum Included DAP DAP DAP DAP DAP MAP MAP MAP MAP
Condensate Pump CPK-7 CPK-3 CPK-3 CPK-5 230V Auto Pump CPK-3 CPK-4 CPK-2 CPK-1

 